The Monsoon Monitor is a manually operated monitor designed for flows up 
to 2,000 gpm (7,600 lpm). Maximum operating pressure is 200 psi (14 
bar). Unique patent pending segmented waterway has only 15 psi (1 bar) 
friction loss at 2,000 gpm. Water makes very few turns as it travels 
though the monitor resulting in low friction loss and a far reaching 
effective stream. Elevation range is 90 degrees above horizontal to 45 
degrees below. Field changeable elevation travel stops at 45 degrees 
above, 30 degrees above, and 30 degrees below horizontal. The manual 
model has continuous horizontal rotation with field changeable stops at 
45, 90, and 135 degrees either side of a center position. Available with
 various inlet flanges and thread fittings. Inlet also made for direct 
connection to TFT's electric Extend-A-Gun RC3 or RC4. Main waterway made
 from hardcoat anodized ANSI 356-T6 aluminum. Silver powder coat finish 
inside and out. Standard outlet is 3.5" (90mm) rigid male thread. Other 
outlets are available. FM approved.